- All products
- Mesurements
- QEED QE-POWER-T-PLUS Three-phase Power Meter and ANALYZER
- Mesurements
QEED QE-POWER-T-PLUS Three-phase Power Meter and ANALYZER
The smallest three-phase network analyser for all current probes. Ready for connection to your monitoring or data logger system. RS485 Modbus RTU
and a configurable digital contact are available. All-in-one input for current transformers and three versions to meet all your needs.
· Three-phase energy meter with universal current input: current transformers with output in voltage or current can be used on the same inputs.
· DIN-rail mounting, perfect for electrical panels.
· Equipped with a serial output RS485 Modbus RTU for forwarding measurement data
· one digital output for alarms. Configuration via free software.
Features of the meter
· Equivalent to class 0.5S (KWh) of EN62053-22
· Equivalent to class 0.5S (KVARh) of EN62053-24
· Accuracy ±0.5% RDG
· Universal input for current measurement: 1/5 A or 0...333mV or Rogowski probe
· Energy meter
· TRMS measurements of distorted sine waves (voltages/currents)
· Current measurement of the neutral conductor
· One digital output (mosfet) for alarms
· Serial RS485 output
· Alarms indicated via LED on the front
· Dimensions: 1 DIN module
Three variants available:
QE- POWER-T-STD
QE-POWER-T-Plus
QE-POWER-T-PRO
Our offering Power measurements.
THREE-PHASE NETWORK ANALYSER - 17.5 mm
QE-POWER-T - Technische specificaties
Accuracy (@25°C, 50 Hz)
|
Parameter |
Reference |
QE-POWER-T |
|
VOLTAGE |
(Un: 230/400 V) |
±0.5% of reading (10...100% Un) |
|
CURRENT |
(In = 5 A) |
±0.5% of reading (5...100% In) |
|
FREQUENCY |
±0.1 Hz of 40...70 Hz |
|
|
POWER |
ACTIVE |
±0.5% of reading |
|
POWER |
REACTIVE |
±0.5% of reading |
|
ENERGY |
ACTIVE |
Class C according to EN50470-1/3 or class 0.5 S according to EN62053-22 |
|
ENERGY |
REACTIVE |
Class 0.5 S according to EN62053-24 |
Overige kenmerken
|
Characteristic |
Value |
|
POWER CONSUMPTION |
< 500 mW @ 24 V DC |
|
SAMPLE RATE |
6400 Hz @ 50 Hz |
|
BAUD RATE RS485 |
from 1200...115200 baud (default 9600) |
|
THERMAL DRIFT |
< 100 ppm/°C |
|
OPERATING TEMPERATURE |
-10°C...+60°C |
|
STORAGE TEMPERATURE |
-20°C...+85°C |
|
RELATIVE HUMIDITY |
10...90%, non-condensing |
|
ALTITUDE |
Up to 2000 m above sea level |
|
MOUNTING SYSTEM |
On DIN rail, prepared for mounting on T-BUS system |
|
CONNECTIONS |
4 removable connectors: 2-, 3- and 6-pole with pitch 3.5 mm; 4-pole with pitch 5.08 mm |
|
DIMENSIONS |
93 x 17.5 x 68.3 mm (without connectors) |
|
WEIGHT |
60 g |
|
DIP SWITCH |
2-pole (baud rate and address) for connection to the configuration software FACILE |
|
LED |
5 LEDs: Power (green), Comm (yellow), TX and RX (red), digital contact (green) |
|
NORM REFERENCES |
EN61000-6-2; EN61000-6-4; EN61000-4-2; EN61000-4-3; EN61000-4-4; EN61000-4-5; EN61000-4-6; EN61010-1; EN61010-2-30 |
|
Meting / functie |
STD |
|
I rms, V rms |
Yes |
|
I pk, V pk per phase |
Yes |
|
P, P1, P2, P3: active power (W) |
Yes |
|
Q, Q1, Q2, Q3: reactive power (VAR) |
Yes |
|
S, S1, S2, S3: apparent power (VA) |
Yes |
|
Frequency |
Yes |
|
Power factor total and per phase (inductive/capacitive) |
Yes |
|
Energy (kWh) total and per phase |
Yes |
|
Bidirectional energy (kWh), positive and negative, per phase and total |
Yes |
|
Active and reactive energy (kVARh) - inductive/capacitive - total and per phase |
Yes |
|
Crest factor total and per phase |
Yes |
|
Tanφ, per phase and average (inductive/capacitive) |
Yes |
|
Average power factor, total and per phase |
YES |
|
Distortion power factor (inductive/capacitive) per phase/average |
YES |
|
THD (V, I) |
YES |
|
Power measurement: minimum, average and maximum per phase and total |
YES |
|
Monitoring of phase sequence |
YES |
|
Maximum demand over 15 minutes, total and per phase |
YES |
|
Time at which the maximum demand occurs (per month), total and per phase |
YES |
|
Time above a threshold value, total and per phase |
YES |
|
K-factor (IEEE Standard 1100-1992) |
YES |
|
Harmonic analysis up to the 63rd harmonic |
No |
|
Interharmonic analysis up to the 63rd harmonic |
No |
|
SAG / SWELL - voltage interruption |
No |

Alternative products
These other products may interest you