AVAILABLE MEASUREMENTS
RS485 Modbus RTU connection: terminals 3 (A+), 4 (B-), 1 (GND)
The device provides power measurements in all 4 quadrants. The sign conventions used in the product are based on the “IEC sign convention for power factor” and are summarised in the following image:
PRODUCT FEATURES

Active power imported/consumed Quadrant 1
W (+)
VAR (+)
PF (+)
Active power Produced Quadrant 2
W (-)
VAR (+)
PF (-)
Active power exported/produced Quadrant 3
W (-)
VAR (-)
PF (-)
Active power imported/consumed Quadrant 4
W (+)
VAR (-)
PF (+)
Using the configuration software or by adjusting the designated registers, the following functions can be configured:
The Modbus address, baud rate, parity, and response time can be set.
Input/output
Three variants available:
QI- POWER-485-50
QI- POWER-485-100
QI- POWER-485-300
Single-phase power meter
QE-POWER-T - Technical specifications
| QI-POWER-485 / QI-POWER-485-100 / QI-POWER-485-300 – Technical specifications | |
| Electrical properties | |
| Supply voltage | 9–30 Vdc with protection against reverse polarity and overtemperature |
| Power consumption | 1.3 W |
| Max. measurement voltage | 80 Vac, 100 Vdc |
| Measurement type | TRMS (AC) / DC |
| Measurement frequency | DC or 1–400 Hz |
| Accuracy class @25 °C up to 200 Hz | Voltage,
current, active power: <0.5% F.S. Frequency: ≤0.1 Hz Energy: ±1% of the measured value Vpeak, Ipeak: <5% F.S. |
| Crest factor | 1.8 (for current measurement) |
| Sampling rate | 11k samples/s |
| Input impedance | 1 MΩ |
| Overvoltage category | Cat
III up to 600 V Cat II up to 1000 V |
| Insulation | 3 kV
on non-connected cable for current measurement 4 kV for voltage measurement (reinforced insulation relative to power and RS485 serial interface) |
| THD | Available for measured currents greater than 15% of F.S. |
| Communication interface | RS485 Modbus RTU |
| Communication properties | |
| Protocol | Modbus RTU |
| Baud rate | 1200–115200 bps (standard 9600) |
| Addresses | 1–247 (standard 1) |
| Data format | 1 start bit, 8 data bits, NO/ODD/EVEN parity (standard no parity) |
| Response time | 1–1000 ms |
| Connection | Via removable 4-pin terminal |
| General data | |
| Operating temperature | -15–60 °C |
| Storage temperature | -40–85 °C |
| Relative humidity | 10–90% non-condensing |
| Altitude | Up to 2000 m above sea level |
| Temperature coefficient | < 200 ppm/°C |
| Protection class | IP20 |

Electrical installation: point of attention
The conductor must be placed as close as possible to the centre of the product to ensure correct current measurement.| Property | QI-POWER-485 | QI-POWER-485-300 |
| Measurable AC/DC current range | up to 50 A RMS | up to 300 A RMS |
These other products may interest you
We use cookies to provide you with a better user experience on this website. Cookie policy